The pattern of dark lights tells you where to look.

Learning Track · Module 6: Faults · Step 39 of 101

Showing content for Europe. Change the region at the top of the page.

What you seeLikely causeSend
Many lights in a row go dark togetherCable cut, joint failure, or blown fuse upstreamCable crew with fault locator
Every third light is darkOne phase lostElectrician to the cabinet
Full circuit darkBreaker or earth leakage trip, contactor, controller, or supplyElectrician to the cabinet
One light dark, neighbours normalDriver, LED module, node, photocell, or pole fuseLamp crew with spares
One light cycles on and offFailing photocell, loose connection, or failing driverLamp crew

USA: For utility lights on overhead lines, a row of dark lights usually means a problem on the secondary line or the transformer. Report it to the utility.

If current on one phase drops by a large step, the fault is on the cable. If it drops by one lamp’s current, the fault is at one pole.