Normal supply limits, and what to do outside them.

Learning Track · Module 6: Faults · Step 40 of 101

Showing content for Europe. Change the region at the top of the page.

Europe: IEC 60038 and EN 50160 give 230 V ±10%: 207 V to 253 V. OpenSLMS uses this band for alarms by default.

Middle East: Most GCC utilities use 230 V with about ±10% (207 V to 253 V). Check the limits in your utility's regulations.

South Asia: Indian supply rules allow about ±6% at low voltage (216 V to 244 V), but real supply often varies more. Many specifications ask drivers to work from 140 V to 300 V. Set alarm limits to match your drivers.

USA: ANSI C84.1 Range A allows ±5% at the service point. For 120 V that is 114 V to 126 V, and for 277 V it is about 263 V to 291 V. Set alarm limits for each supply voltage.

Low voltage

  • Long cable with too small a cross-section.
  • Too much load on one phase.
  • A loose or corroded joint.
  • Low supply from the network.

High voltage

A lost neutral is the most dangerous cause. Lights on a lightly loaded phase can get close to phase-to-phase voltage. This destroys drivers fast. Treat a sudden high voltage on one phase as Critical.

Surge protection devices in the cabinet and each luminaire protect against lightning and switching surges. Check their status at each preventive visit.