With no clear fault.

Learning Track · Module 7: Failure library · Step 58 of 101

SymptomThe circuit trips at night, often in wet weather, and resets.
CauseMany small leakage currents from drivers and filters add up on a long circuit, or a real insulation fault starts in wet weather.
CheckMeasure leakage current with a leakage clamp. Test each section's insulation. Split the circuit to find the section.
FixRepair the insulation fault. If leakage from many drivers is the cause, split the circuit, as the rules permit.
PreventLimit the number of drivers per protected circuit. Check driver leakage current on the datasheet.

Warning

Never bypass the device to keep lights on.

Related across the playbook: Earth leakage and electrical safety: A live pole is the most dangerous fault on the network.