Negative power or impossible power factor.

Learning Track · Module 7: Failure library · Step 56 of 101

SymptomNegative kW, power factor near zero, or energy on the wrong phase.
CauseA current transformer fitted the wrong way, or CTs and voltage inputs on different phases.
CheckCompare each phase with a clamp meter. Check CT direction arrows and phase labels.
FixTurn or move the CT. Correct the wiring. Commission again.
PreventFollow the commissioning SOP before you accept the data.