Drivers fail on one phase, lights flicker on others.

Learning Track · Module 7: Failure library · Step 49 of 101

SymptomSudden high voltage on one phase and low voltage on another. Many drivers on the high phase fail at once.
CauseA broken or loose neutral at the cabinet, in a cable joint, or in the supply.
CheckMeasure phase-to-neutral voltage on each phase. Measure neutral current. Check neutral terminals and joints.
FixRepair the neutral. Replace damaged drivers. Check the full circuit before you restore it.
PreventAlarm on voltage outside limits. Tighten neutral terminals at each visit. Balance the load across phases.

Warning

Treat as Critical. A lost neutral can also make exposed metal live.