Fuse blows or earth leakage trips after rain.

Learning Track · Module 7: Failure library · Step 45 of 101

SymptomOne or more lights go dark after rain. The earth leakage device trips. The pole fuse is blown or corroded.
CauseDamaged gasket, open cable entry, or a pole door that does not close. Water collects at the base of the pole.
CheckIsolate. Open the door. Look for water, rust, green corrosion on terminals, and tracking marks. Test insulation resistance.
FixDry the box. Replace corroded terminals and fuse carrier. Seal cable entries. Replace the gasket or door.
PreventRaise the box above ground level. Use IP-rated junction boxes with drip loops. Check gaskets before the wet season.